UC400 S23 Cat.6 U/FTP
Technical data:
UC400 S23 Cat.6 U/FTP
Construction
1. Conductor bare copper wire ∅ 0.56 mm (AWG 23)
2. Insulation Foamskin Polyethylene, ∅ 1.35 mm
3. Twisting 2 cores to the pair
4. Pair screen High Performance STP: Al-laminated plastic foil, patented wrapping of two pairs each, drain wire AWG 26 tinned
5. Cable lay up 2 x 2 pairs to the core
6. Sheath PVC alt. FRNC, blue RAL 5012
Duplex sheath: two cables parallel, separable
Technical specification
Bending radius:
≥ 35 mm without load
≥ 70 mm with load
Temperature range during operation: –20 °C up to +60 °C
Temperature range during installation: 0 °C up to +50 °C
Application: Primary (Campus), Secondary (Riser), Tertiary (Horizontal)
IEEE 802.3: 10Base-T; 100Base-T; 1000Base-T; IEEE 802.5 16 MB; ISDN; TPDDI; ATM
Standards:
EIA/TIA 568B; ISO/IEC 11801 2nd ed.; IEC 61156-5; EN 50173; CLC/ TC215 (Sec)94; prEN 50288-5-1
Fire rating
PVC: IEC 60332-1
FRNC: IEC 60332-1; IEC 60754-2; IEC 61034
FRNC-C: additionally IEC 60332-3 C
Electrical Properties (at 20±5 °C)
DC loop resistance: ≤ 176 Ω/km
Resistance unbalance: ≤ 2 %