Friday, 18. May 2012 | 06:07 h

 
 

N(F)2XS(FL)2Y 18/30 (36) kV

nf2xsfl2y_18_30_36_kvMedium Voltage Cables
Technical data:  N(F)2XS(FL)2Y 18/30 (36) kV

 


Construction
Conductor: Stranded, round and compacted
copper acc. to EN 60228, class 2
Conductor screen: Extruded
Insulation: XLPE, nom. thickness 8.0 mm
Insulation screen: Extruded bonded
Separator: Semi conducting water blocking
tape
Concentric
conductor: Annealed copper wires and counter
spiral of copper-tape
Separator: Semi conducting water blocking
tape
Radial water
sealing: Aluminium tape
Sheath: PE, black
Marking e.g.: N2XS(FL)2Y 18/30 (36) kV
1 x 70 RM/16 DRAKA,
manufacturing year,
number of particular length,
VDE 0276-620, meter marking
Design standard
HD 620 part 5, section C (VDE 0276)
Temperature range
In continuous operation max. +90 ºC. Lowest cable
temperature during installation: -20 ºC and below 0 ºC
special precaution shall be taken.
Impulse voltage
180 kV
Bending radius
At fixed mounting: 10 x D
At laying: 15 x D
Use
Single-core, distribution cable for outdoors and indoors
use in 3-phase formation. Installation in pipes and
ground/water.