Friday, 18. May 2012 | 06:13 h

 
 

AXPK/AXMK

axpk-axmk 1 kV underground power cable with aluminium conductors and XLPE insulation

Technical data:
AXPK/AXMK


CONSTRUCTION
1. Aluminium conductor solid, class 1, or stranded, class 2
2. XLPE insulation
3. Filler layer
4. PVC shealth

TECHNICAL SPECIFICATION
Rated voltage: U0/U = 0,6/1 kV
Um = 1,2 kV
Highest permissible conductor temperature:
- in continuous operation: +90 °C
- in a short circuit (max. 5 s): +250 °C
Lowest recommended temperature during laying: -15 °C
Min. permissible bending radius during laying: 12 D
Min. permissible bending radius after a final installation: 9 D
Use: Fixed indoor, outdoor and underground installations
Colour of sheath: black
Identifikaction of cores: HD 308 S2:2001 - Idt. ČSN 33 01 66 ed. 2
Manufactured according to: SFS 4879, HD 603-5D S1, IEC 60502-1
Standard  packing: drums