Technical data:  DRAKA Fire-ret 1-CXKH-R


Construction
1. Copper conductor solid, class 1, or stranded, class 2
2. Insulation of halogen-free cross-linked polyethylene compound
3. Taped or extruded filler layer, halogen-free
4. Halogen-free outer sheath, flame retardant

Technical specification
Rated voltage: 0.6/1 kV
Test voltage: 4 kV
Perm. operating temperature:
– flexible use: min. –5 °C max. +50 °C
– fixed installation: min. –30 °C max. +90 °C
Min. perm. temp.
– with installation and handling: +4 °C
– storage: –30 °C
Max. perm. storage temp.: +40 °C
Use:
Suitable for dry or moist rooms, also for outdoor usage, but unsuitable for direct laying in the ground or in water.
Colour of sheath: orange (RAL 2010), or other on request
Marking of cores according to: DIN VDE 57293 / VDE 0293 Idt. HD 308 S2
Standard packing: drums, coils
Fire propagation in bundles according to: EN 50266-2-2; IEC 60332-3-22
Halogen free, corrosivity of ermitted gasses according to: EN 50267-1,2-2; IEC 60754
Smoke density according to: EN 50268-1-2; IEC 61034-1,2
Self-extinguishing according to: IEC 60332-1