EMC LINE 1 kV (IFSI) - copper conductor
Technical data:
EMC LINE 1 kV (IFSI)
CONSTRUCTION
1. Copper conductor solid, class 1, or stranded, class 2
2. Insulation: cross-linked halogen-free polymer
3. Bedding/tape: halogen-free
4. C oncentric conductor (PE/PEN-conductor): Cross-sections 1,5–2,5 mm2 have aluminium tape with drain wire. Cross-sections ≥4 mm2 have copperfoil with overlap and concentric screen of copper wires
5. Outer sheath: halogen-free polymer
TECHNICAL SPECIFICATION
Rated voltgate: 0,6/1kV
Test voltage: 4 kV
Max. conductor temp.:. +90 °C
Perm. temperature for fixed installation.: min. -40 °C max. +90 °C
Min. perm. temp.:
- with installation and handling: +4 °C
- storage: -40 °C
Use:
Halogen-free cable for indoor and outdoor use, to secure areas from heavy smoke and corrosive gases in case of fire. Cable meet characters of EMC (electromagnetic compatibility).
Colour of sheath: black
Standard packing: drums
Note: Flame retardant according to IEC 60332-1; flame retardant in bundles according to IEC 60332-3-24.