FIRETUF® NHXH FE180/E30
Halogen-free fire resistant cables with functionality of electric cable system
Technical data:
FIRETUF® NHXH FE180/E30
CONSTRUCTION
1. Copper conductor solid, class 1, or stranded, class 2
2. Double insulation of mica tape and cross-linked HI1 polymer
3. Fire resistant glass tape applied over cores
4. Orange sheath of HM4 polymer compound, flame retardant
TECHNICAL SPECIFICATION
Rated voltage: 0.6/1 kV
Test voltage: 4 kV
Perm. operating temperature: min. –30 °C max. +90 °C
Min. perm. temp.
- with installation and handling: +4 °C
- storage: -30 °C
Use: Suitable for dry or moist rooms, also for outdoor usage, but unsuitable for direct laying in the ground or in water.
FE180: Insulation integrity for 180 min., tests according to DIN VDE 0472 Part 814, IEC 60331.
E30: Functionallity of electric cable system for duration of at least 30 min., test according to DIN VDE 4102 Part 12.
Colour of sheath: orange (RAL 2010), brown (RAL 8003), or other on request
Marking of cores according to: 57293/VDE 0293 – Idt. HD 308 S2
Standard packing: drums, coils
Note: Flame retardation according to DIN-VDE 0472, Part 804