SAX-W (PAS-W) 20 kV
20 kV insulated aerial conductor SAX-W (PAS-W)
Technical data:
SAX-W (PAS-W) 20 kV
CONSTRUCTION
1. Round, stranded and compacted watertight aluminium alloy conductor
2. XLPE insulation
TECHNICAL SPECIFICATION
Rated voltage:
U0/U = 12/20 kV
Um = 24 kV
Maximum permissible conductor temperature
– in continuous operation: +80 °C
– in a short circuit
(max. 5 s): +200 °C
Min. recommended temperature during installation: –20 °C
Min. permissible bending radius during installation: 14 D
Min. permissible bending radius after a final installation: 10 D
Use:
For pole installation as part of PAS-system.
Colour of sheath: black
Manufactured according to: HD 50397
Standard packing: drums
Declaration of conformity:
PAS-W 