Tuesday, 22. May 2012 | 00:32 h

 
 

SE-N1XE-U/-R/-AS 0,6/1 kV (1-CXKE, 1-AXKE)

se-n1xe-u--r--as-0_6-1-kv Underground power cable

Technical data:
SE-N1XE-U/-R/-AS 0,6/1 kV


CONSTRUCTION
1.Copper conductor solid, class 1, or stranded, class 2; aluminium conductor stranded, class 2
2. XLPE insulation
3. Filler of extruded compound or plastic tape
4. PE sheath

TECHNICAL SPECIFICATION
Rated voltage: U0/U = 0.6/1 kV
Maximum permissible conductor temperature in continuous operation:: +90 °C
Minimum recommended temperature during laying: –20 °C
Min. permissible bending radius at fixed mounting: 8 D
Min. permissible bending radius at pulling-in: 12 D
Min. permissible bending radius at ploughing-down: 8 D
Use:
Open, fixed installation, outdoors, in pipes and in ground/water. Not in rooms where explosions may occur. Very suitable to plough down.
Colour of sheath: black, yellow
Indentification of cores:
4-core: brown, black, grey, green/yellow
5-core: blue, brown, black, grey, green/yellow
Fire propagation class: F1 acc. to SS 424 14 75
Manufactured according to: SS 424 14 18 CENELEC HD 603 Part 5 Section O
Standard packing: drums 500 m