Tuesday, 22. May 2012 | 00:58 h

 
 

TMP-NSSHOEU, TMP-NTSWOEU TENAX®-TMP

tmp-nsshoeu-tmp-ntswoeu-tenax-tmpSubmersible cable, DIN VDE 0250, Parts 812 and 813, rated voltage up to 6 kV

Technical data: TMP-NSSHOEU, TMP-NTSWOEU TENAX®-TMP


CONSTRUCTION
1. Flexible tinned copper conductor, class 5
2. Core insulation of rubber compound of type 3GI3 based on EPR (1 kV cables have coloured marking)
3. Inner sheath of synthetic rubber of type GM1 b with extra low water absorption and permeability of water vapours
4. Outer sheath of chlorinated rubber compound of type 5GM3 or 5GM5

Application
For connection of electrical service equipment in industrial water, particularly for submersible pumps. Three-core cables without earth conductors are used at places where riser pipes serve as an earth conductor.

TECHNICAL SPECIFICATION

Rated voltage U0/U: 0.6/1 kV, 1.8/3 kV, 3.6/6 kV
Bending radius:
- fixed installation min. 4 x D (TMP-NSSHOEU)
min. 6 x D (TMP-NTSWOEU)
- flexing min. 5 x D (TMP-NSSHOEU)
min. 10 x D (TMP-NTSWOEU)
Temperature range:
- fixed installation min. -40 °C max. +80 °C
- flexing min. -25 °C max. +80 °C
Colour of sheath:
yellow (TMP-NSSHOEU)
black (TMP-NTSWOEU)

ALTERNATIVE CONSTRUCTIONS
TMP-NSSHOEU has yellow outer sheath of chlorinated rubber compound 5GM5, abrasion, tear and oil resistant, self-extinguishing.

TMP-NTSWOEU has red outer sheath of chlorinated rubber compound 5GM3, oil resistant, self-extinguishing.

Special constructions on request e.g. armoured medium voltage cables for use in maritime drilling machines and for extreme submersion depths up to 1 000 m.